No ads, no sign-upChecked 2026-10-06

Voltage Drop Calculator

Your numbers

Change any value to update the result.

Drop · share · load voltage

3.36 V · 2.8 % · 116.64 V at load

Drop · share · load voltage: 3.36 V · 2.8 % · 116.64 V at load
In other units
65.617 ft
Examples

Enter current, one-way length and supply voltage. Choose DC, single-phase or balanced three-phase and a conductor. Read drop in V and %, plus voltage at the load. AC presets use Schneider's XLPE table for lighting (cos φ=1) or motors (0.8); manual AC is a resistance-only estimate, not a wiring approval.

The numbers at a glance

Held fixed: Circuit DC, Current (A) 10.000 A, One-way run length 20.000 m, Supply voltage (V) 120.00 V, Conductor / cross-section Manual ρ / cross-section, AC load model (ignored for DC) Lighting, cos φ = 1, Resistivity (manual only) 0.000000016800 Ω·m.

Cross-section (manual only) (m²)Drop · share · load voltage
0.00000050000013.44 V · 11.2 % · 106.56 V at load
0.0000010000006.72 V · 5.6 % · 113.28 V at load
0.0000015000004.48 V · 3.733 % · 115.52 V at load
0.000002000000Your value3.36 V · 2.8 % · 116.64 V at load
0.0000025000002.688 V · 2.24 % · 117.312 V at load
0.0000030000002.24 V · 1.867 % · 117.76 V at load
0.0000035000001.92 V · 1.6 % · 118.08 V at load
0.0000040000001.68 V · 1.4 % · 118.32 V at load

Worked examples

Case 1

Circuit
DC
Current (A)
10A
One-way run length
20m
Supply voltage (V)
120V
Conductor / cross-section
Manual ρ / cross-section
AC load model (ignored for DC)
Lighting, cos φ = 1
Resistivity (manual only)
1.68e-8Ω·m
Cross-section (manual only)
0.000002m²

3.36 V · 2.8 % · 116.64 V at load

Open with these values

Case 2

Circuit
DC
Current (A)
15A
One-way run length
30m
Supply voltage (V)
120V
Conductor / cross-section
Manual ρ / cross-section
AC load model (ignored for DC)
Lighting, cos φ = 1
Resistivity (manual only)
1.68e-8Ω·m
Cross-section (manual only)
0.000004m²

3.78 V · 3.15 % · 116.22 V at load

Open with these values

Case 3

Circuit
DC
Current (A)
20A
One-way run length
50m
Supply voltage (V)
120V
Conductor / cross-section
Manual ρ / cross-section
AC load model (ignored for DC)
Lighting, cos φ = 1
Resistivity (manual only)
2.82e-8Ω·m
Cross-section (manual only)
0.000006m²

9.4 V · 7.833 % · 110.6 V at load

Open with these values

How it's calculated

DC: ΔV = 2ILρ/A; AC presets: ΔV = KIL (L in km, K from cable table)

  1. StepChoose DC, single-phase or balanced three-phase and enter current, supply voltage and one-way cable length.Current (A)=10A·Supply voltage (V)=120V·One-way run length=20m
  2. StepSelect a copper/aluminium size; for manual input, enter resistivity and cross-section in m².Resistivity (manual only)=0.0000000168Ω·m
  3. StepFor AC presets, choose the lighting or normal motor load table; the cable assumptions come from the cited source.AC load model (ignored for DC)=Lighting, cos φ = 1
  4. ResultRead volts lost, percentage of supply and load-end voltage for this run only; upstream drop is excluded.Supply voltage (V)=120V·AC load model (ignored for DC)=Lighting, cos φ = 1→3.36 V · 2.8 % · 116.64 V at load

Reference table

Mode, current, one-way length, conductorWhat that run isVoltage drop (V)
5, 10, 0.0000000168, 0.00000155 A over 10 m of 1.5 mm² copper1.12
30, 25, 0.0000000168, 0.0000130 A over 25 m of 10 mm² copper2.52
10, 20, 0.0000000168, 0.00000210 A over 20 m of 2 mm² copper3.36
15, 30, 0.0000000168, 0.00000415 A over 30 m of 4 mm² copper3.78
20, 50, 0.0000000282, 0.00000620 A over 50 m of 6 mm² aluminium9.40
Single-phase, 20 A, 20 m, Cu 2.5 mm²Schneider lighting table, K = 19 V/A/km7.60
Three-phase, 100 A, 50 m, Cu 35 mm²Schneider motor table, K = 1 V/A/km5.00

Questions

How do I calculate voltage drop?

For manual DC, use 2 × one-way length × current × resistivity / area. The selected AC cable tables already include the circuit and load factors; multiply their K by amperes and one-way kilometres.

Why do I enter the one-way length?

DC and single-phase circuits include the return path; balanced three-phase uses a different phase factor. Enter the distance from supply to load once: the formula or sourced cable coefficient handles the circuit path.

What do the AC cable presets assume?

The cited Schneider table models copper or aluminium XLPE cable, with lighting at cos φ = 1 or motor normal service at cos φ = 0.8. Its rounded K values include resistance, reactance and circuit geometry; manual AC input omits reactance and is only a resistance-based approximation.

Does a low percentage mean the cable is safe?

No. This result estimates voltage loss on the entered run only; it excludes upstream loss, ampacity, overcurrent protection, installation method and local code requirements. Have a qualified professional assess an actual installation.

What units can I enter?

The one-way distance accepts metres or feet; the calculator converts feet internally. Cable presets are named by mm², while the legacy manual cross-section is entered in m² (1 mm² = 0.000001 m²). Supply and load voltages use the same V basis.

Can I estimate DC wire heating from this result?

For the simple DC run, current times voltage drop estimates heat lost in the pair of conductors. The three-phase AC loss is not generally obtained by multiplying its displayed line-to-line drop by current.

Sources and last check

  1. electrical-installation.org

Information, not professional advice.